Category 6A (625MHz), 4-Pair, S/FTP shielded, Premise Horizontal Cable, 23 AWG Solid Bare Copper conductors, Foam Polyethylene insulation, each pair with Beldfoil® shield, tinned copper braid shield (30%), LSZH jacket, CPR Euroclass Eca
Product Overview:
Suitable Applications
Horizontal and building backbone cable; Support current and future Category 6A and 6 applications, such as: 10GBase-T (10 Gigabit Ethernet), 1000Base-T (Gigabit Ethernet), 100 Base-T, 10 Base-T, FDDI, ATM
CONDUCTOR
Element
Individual shielded pair
Number of Pairs
4
AWG
23
Stranding
Solid
Material
BC - Bare Copper
Conductor Count
8
Total Number of Pairs
INSULATION
Type
Dielectric
PE - Polyethylene (Foam)
Thickness
0.029 in
Nom. Diameter
1.32 mm
Bonded-Pair
No
COLOR CHART
Number
Color
Pair 1
White & Blue
Pair 2
White & Orange
Pair 3
White & Green
Pair 4
White & Brown
INNER SHIELD MATERIAL
Tape
Bi-Laminate (Alum+Poly)
Coverage [%]
100%
Table Notes
Aluminum facing outside
CABLING
Description
4 pairs twisted together
OUTER SHIELD MATERIAL
Outer Shield Type
Braid
Tinned Copper (TC)
Min. Coverage [%]
30%
OUTER JACKET MATERIAL
LSZH - Low Smoke Zero Halogen (Flame Retardant)
Nominal Diameter
7.0 mm
Diameter +/- Tolerance
0.3 mm
Ripcord
Yes
Construction and Dimensions
Min Elongation at Breakof Conductors
10 %
Min Elongation at Breakof Insulation
100 %
Min Elongation at Breakof Jacket
Min Tensile Strength of Jacket
9 MPa
Electrical Characteristics
Max. Conductor DCR
95 Ohm/km
Max DCR Unbalanced Between Pairs [%]
4 %
Max. DCR Unbalanced Within Pair [%]
2 %
Max. Capacitance Unbalance
1,600 pF/km
Max. Mutual Capacitance
56 pF/m
Nominal Characteristic Impedance
100 Ohm
Max. Delay Skew
45 ns/100m
Nominal Velocity of Propagation (VP) [%]
77%
TRANSFER IMPEDANCE
Frequency [MHz]
Transfer Impedance
1 Mhz
Max. 50 mOhm/m
10 Mhz
Max. 100 mOhm/m
30 Mhz
Max. 200 mOhm/m
100 Mhz
Max. 1000 mOhm/m
Transfer Impedance Class
Grade 2
Max. Recommended Current [A]
1.5 Amps per Conductor
Voltage Rating [V]
72 V
Installation Temp Range
0°C To +50°C
Operating Temp Range
-30°C To +60°C
Bulk Cable Weight
52 kg/km
Max. Pull Tension
85 N
Min. Bend Radius During Installation
58mm
Min Bend Radius During Operation
29 mm